NEOMITIS THERMOSTAT
- Does the thermostat display state "LOW" or is the screen blank?
YES = Change the batteries in the thermostat allowing up to 10 minutes before putting new ones in. - Are there any lights on the receiving unit (located on the wall near the boiler)?
NO LIGHTS/RED = Needs reconnecting with the boiler. See manual below
GREEN = They are connected. Check times and temperatures See manual below
QUICK RESYNC
Press and hold the RF test on the reciver for 5 seconds and it should start flashing green.
Press and hold the RF test button on the thermostat and the 'PAIR' icon will start flashing.
The reciever will have a solid green light when pairing is complete.
For further assistance please use the following link -
https://neomitis.com/sites/neomitis/lMG/pdf/instruction manual rtl.pdf
Press and hold the RF test on the reciver for 5 seconds and it should start flashing green.
Press and hold the RF test button on the thermostat and the 'PAIR' icon will start flashing.
The reciever will have a solid green light when pairing is complete.
For further assistance please use the following link -
https://neomitis.com/sites/neomitis/lMG/pdf/instruction manual rtl.pdf